Free shop air tool
Dust collection CFM calculator
Total the airflow your machines actually need, get a main duct size that keeps dust moving, and sanity-check the velocity in any duct. Built on the standard sizing method: simultaneous machines and a 3,500 to 4,500 FPM velocity window.
Calculator
Count only the machines that run at the same time. Blast gates close the rest.
CNC router
800 CFM
1Table saw
350 CFM
1Planer
500 CFM
0Jointer
400 CFM
0Bandsaw
400 CFM
0Shaper
500 CFM
0Router table
350 CFM
0Miter saw
350 CFM
0Drum sander
550 CFM
0Wide belt sander
1,500 CFM
0Edgebander
600 CFM
0Lathe
400 CFM
0Floor sweep
350 CFM
0
Airflow needed
1,150 CFM
- Suggested main duct
- 7″
- Velocity in that main
- 4,303 FPM
Pick a collector rated comfortably above this number at your system's static pressure, and add 20 to 30% headroom for filter loading and future machines.
Machine values are typical planning numbers; your machine’s spec sheet wins. For multi-machine systems, static pressure and branch balancing matter as much as CFM.
The math behind duct sizing
Airflow, duct area, and velocity are locked together. Pick any two and the third follows.
Duct area (sq ft)
π × (D ÷ 2)² ÷ 144
A 6" round duct has a cross-section of about 0.196 square feet.
Air velocity (FPM)
CFM ÷ duct area
785 CFM through that 6" duct moves at about 4,000 feet per minute.
System airflow
Sum of machines running at once
Blast gates close idle branches, so you size for simultaneous use, not the whole shop.
CFM requirements by machine
Typical planning values for common woodworking machines. Larger machines, multiple ports, and heavy chip producers (moulders, wide belt sanders, nested CNC routers) run higher, so check the manufacturer’s spec when you have it.
The branch duct to each machine is sized to that machine. The main is sized to whatever combination runs at once.
| Machine | Typical CFM | Branch duct at ~4,000 FPM |
|---|---|---|
| CNC router | 800 | 6″ |
| Table saw | 350 | 4″ |
| Planer | 500 | 5″ |
| Jointer | 400 | 5″ |
| Bandsaw | 400 | 5″ |
| Shaper | 500 | 5″ |
| Router table | 350 | 4″ |
| Miter saw | 350 | 4″ |
| Drum sander | 550 | 5″ |
| Wide belt sander | 1,500 | 8″ |
| Edgebander | 600 | 5″ |
| Lathe | 400 | 5″ |
| Floor sweep | 350 | 4″ |
How much air a duct can carry
CFM capacity of standard round duct across the healthy velocity window. Read it either way: find your airflow and see what duct fits, or find your duct and see what airflow it wants.
| Duct diameter | 3,500 FPM | 4,000 FPM | 4,500 FPM |
|---|---|---|---|
| 4″ | 305 CFM | 349 CFM | 393 CFM |
| 5″ | 477 CFM | 545 CFM | 614 CFM |
| 6″ | 687 CFM | 785 CFM | 884 CFM |
| 7″ | 935 CFM | 1,069 CFM | 1,203 CFM |
| 8″ | 1,222 CFM | 1,396 CFM | 1,571 CFM |
| 9″ | 1,546 CFM | 1,767 CFM | 1,988 CFM |
| 10″ | 1,909 CFM | 2,182 CFM | 2,454 CFM |
| 11″ | 2,310 CFM | 2,640 CFM | 2,970 CFM |
| 12″ | 2,749 CFM | 3,142 CFM | 3,534 CFM |
| 14″ | 3,742 CFM | 4,276 CFM | 4,811 CFM |
CFM fills the brochure. Velocity moves the dust.
A collector’s advertised CFM is measured wide open, with no duct attached. Bolt on a real system, with its elbows, flex hose, and filters, and the delivered airflow drops with every foot of resistance. That’s why systems that look right on paper still leave piles under the saw.
Velocity is the number that does the work. Keep the air in the duct moving around 4,000 feet per minute and chips ride the stream all the way to the collector.
Let it sag, and the heaviest material drops out in the longest horizontal run, the pile grows, and one day the system chokes. Oversized duct is the usual cause: bigger pipe feels generous, but the same airflow through more area means slower air.
The fix is a system designed as a whole: mains and branches sized together, gates on idle machines, smooth pipe over flex, and a collector picked from its fan curve, not its headline.
Dust collection FAQs
How many CFM do I need for dust collection?
Add up the CFM requirements of the machines that run at the same time, not every machine in the shop. A typical table saw wants around 350 CFM, a planer around 500, and a CNC router 800 or more. A one-person shop where only one machine runs at a time can size for its hungriest machine; a production floor sizes for the worst-case combination, plus 20 to 30% headroom.
What air velocity does dust collection need?
Roughly 3,500 to 4,500 feet per minute in the duct. Below about 3,500 FPM, wood chips and dust fall out of the airstream and pile up in horizontal runs until the duct chokes. Much above 4,500 FPM, you pay a penalty in static pressure, noise, and duct wear without collecting any better.
What size duct should I use?
The size that carries your airflow inside that velocity window. At 4,000 FPM, a 5-inch duct carries about 545 CFM, a 6-inch about 785, a 7-inch about 1,070, and an 8-inch about 1,400. Use the calculator's duct check to test any combination, and remember branches to single machines are sized to that machine, while the main is sized to the total.
Why is my dust collector not keeping up?
The usual suspects, in order: clogged or loaded filters, too many open blast gates dropping the velocity everywhere, long runs of corrugated flex hose (which has two to three times the resistance of smooth pipe), leaks at joints, an undersized main, or a collector whose advertised CFM was measured with no duct attached. Real systems lose a lot to static pressure.
Does duct length matter, or just diameter?
Both. Every foot of pipe, every elbow, and every flex section adds static pressure that the collector must overcome, and its delivered CFM drops as resistance rises. Keep runs short and straight, use long-radius elbows, keep flex hose to the last few feet at the machine, and check the collector's fan curve rather than its headline CFM.
Can I use PVC pipe for dust collection?
Small hobby systems sometimes do, with grounding wire to control static. For a business, smooth-wall metal duct is the standard: it handles the airflow better, it's groundable, and commercial shops need to meet combustible dust requirements (NFPA standards and local fire code) that PVC systems generally don't. When in doubt, ask your insurer what they expect to see.
What about the fine dust I can't see?
The visible chips are a housekeeping problem; the invisible dust under 10 microns is the health problem, and it's exactly what cheap filters pass straight back into the shop air. Look at the filtration rating of the collector, not just its CFM, and for production environments consider properly rated filter media or HEPA-class filtration and ambient air cleanup.
When should I get an engineered system instead of guessing?
When multiple machines run at once, when you're adding a CNC router or wide belt sander, or when fire code and insurance are involved. An engineered system balances duct sizes branch by branch so every machine sees the right velocity. That's exactly the work we do with Nederman industrial dust collection.
Ready for dust collection that actually keeps up?
We design, size, and install industrial dust collection built around Nederman systems: engineered ducting, the right collector for your machines, and filtration that protects the people in the building, not just the floor. Tell us what’s running and we’ll spec it properly.